Glossary

Water supply and EPANET terms as Indian municipal engineers use them, in plain English.

The same glossary, with a search box, is on the Glossary tab of Help > PipePilot Help.

TermMeaning
NodeAny point in the model where pipes meet or water enters or leaves: a junction, reservoir or tank.
JunctionA node where pipes join and where consumer demand is drawn.
LinkAnything that carries water between two nodes: a pipe, pump or valve.
PipeA link that carries water from one node to another, losing head to friction on the way.
PumpA link that adds head to lift water to a higher level or push it further.
ValveA link that controls pressure or flow at one point in the network.
Sluice valveAn isolation valve that is fully open or fully closed; modelled as a pipe set Open or Closed.
PRV (pressure reducing valve)A valve that keeps downstream pressure at or below its setting, used for low lying zones.
NRV (non-return valve)A valve that lets water flow one way only; modelled as a pipe with status CV.
Air valveA valve at high points that releases trapped air. Not modelled in EPANET, but it matters on rising mains.
ReservoirIn EPANET, a source with a fixed water level that never runs dry, such as a treatment plant or large lake.
TankStorage whose water level rises and falls as it fills and empties during the day.
ESR (elevated service reservoir)An overhead tank on staging that supplies a zone by gravity. Modelled as a Tank.
GSR (ground service reservoir)A storage tank at ground level, often feeding a pump that lifts water to an ESR.
SumpAn underground or ground level tank that pumps draw from.
ElevationHeight of a point above a common datum, usually mean sea level, in metres.
HeadEnergy of the water expressed as a height in metres: elevation plus pressure head.
HGL (hydraulic grade line)The line joining the head at each point along a main. Ground above the HGL means negative pressure.
PressureForce of the water on the pipe, reported in metres of water column in metric units.
Residual pressurePressure left at the ferrule while water is being drawn. CPHEEO 2024 (Part A s.2.10.2 p.58, Table 2.7 S.No.10 p.77) asks for 17 to 21 m in Class I and II cities (17 m minimum, 21 m target) and 12 to 15 m elsewhere; rural 7 m (12 m with a flow control valve).
DemandWater drawn from the network at a node, as a flow rate.
Base demandAverage demand at a junction before the time pattern is applied.
lpcdLitres per person per day. CPHEEO: 135 lpcd, or 150 lpcd for cities above 10 lakh, plus 15% for losses. JJM rural target: 55 lpcd.
PatternA list of multipliers, usually 24 hourly values, that makes demand rise and fall over the day.
Peak factorRatio of peak hour demand to average demand. CPHEEO uses 2.5 for urban and 3 for rural supply.
FlowVolume of water passing per unit time, for example litres per second (LPS).
VelocityAverage speed of water in a pipe. CPHEEO 2024 gives 0.6 to 3 m/s for filtered water.
DiameterInternal diameter of a pipe, in millimetres. CPHEEO suggests 100 mm minimum for primary distribution pipes.
HeadlossHead lost to friction and fittings as water flows. CPHEEO limits the gradient to 10 m per km.
RoughnessHow rough a pipe wall is. With Hazen-Williams, a higher C means a smoother pipe and less headloss.
Hazen-Williams CThe roughness value most Indian designs use: 145 for PVC and HDPE, 140 for lined DI, 100 for unlined CI (CPHEEO 2024 Table 6.2).
Rising mainA pipe that carries water from a pump to a tank, under pump pressure.
Gravity mainA pipe that carries water downhill from a higher tank or source without pumping.
Distribution networkThe pipes that carry water from service tanks to consumers.
Steady state (snapshot)A run for a single moment, with Total Duration 0. Good for checking peak hour pressures.
EPS (extended period simulation)A run over time, usually 24 hours or more, so tanks fill and empty and demand follows its pattern.
Intermittent supplySupply for only a few hours a day. Pressure driven analysis models it better than demand driven.
24x7 supplyContinuous pressurised supply to every connection, the goal of many AMRUT and Smart City schemes.
DMA (district metered area)A zone with metered inflow and closed boundary valves, so its losses can be measured.
NRW (non-revenue water)Water produced but not billed: leaks, theft and meter errors.
FerruleThe small fitting that taps a house connection off the distribution main. Residual pressure norms are measured here.
House service connectionThe pipe from the ferrule to the consumer's tap or meter.
FHTC (functional household tap connection)Jal Jeevan Mission term for a rural household tap that delivers at least 55 lpcd of potable water regularly.
EmitterA junction outflow that grows with pressure. Used in EPANET for leaks and hydrants.
Pressure driven analysis (PDA)A run where junctions receive less water when pressure is low, as in a real intermittent network.
Residual chlorineChlorine left in the water at the consumer end, which protects against recontamination.
Water ageHow long water has been in the network since leaving the source. High age means weak chlorine.
CalibrationAdjusting roughness, demands and levels until model pressures and flows match field readings.